High Efficiency four Pass FBC Solid Fuel Fired Thermic Fluid Heater

 

Combustion Technology
Complete Combustion Of Solid Fuel Is Achieved By Through Mixing Of Fuel, Air And A Self Sustainable Combustion Temperature Ensured By Adequate Oxygen To Every Particle Of Fuel.

Every Solid Fuel Has Different Physical And Chemical Properties Which Influences The Design And Performance Of The Furnace In Thermic Fluid Heater. Different Combustion System Are Shown In Above Diagram.

Low Grade Flues Are Best Handled Using Fbc Technology To Give Good Results. Shivotherm Unique Design For Efficient Combustion To Suit Different Solid Fuels, Like Coal, Lignite, Wood Waste, Husk, Petcoke, Bagasses & Biomass Fuels Results In To Low Operating Cost, Trouble Free Operation And Lesser Maintenance.

Fluidised Bed Combustion
Fluidised Bed Combustion Technology Is Best Suited For Some Of The Fuels Like Low Grade Coal, Paddy Husk, Agro Wastes, Etc.. With High Ash Content.

Fbc Technology Ensures:
1. Homegeneous Mixing Of Fuel Ensuring Efficient Combustion Due To High Turbulence In Bed.
2. Automatic Operation For Consistent Performance, Hence Less Dependency On Labors During Continuous Operation.
3. Efficient Combustion Of Low Grade Fuels.

 

Auto Controls & Safeties

1. Thermic Fluid Temperature Control
Digital Temperature Indicator Cum Controller Cut-Off Id/Fd Fan At Preset Temperature  And Restart At Preset Differential Temperature To Maintain System Temperature.

2. Stack Temperature Control
A Blind Temperature Controller Cut Of Id/Fd Fan & Sound Alarm If Stack (Flue Gas) Temperature Exceeds To Preset Temperature.

3. Low / No Flow Of Thermic Fluid
Differential Pressure Switch Connected Across Inlet & Outlet Headers Signals Low Flow Alarm In Case Of Low Fluid Pressure Of Thermic Fluid In Coils.

4. Low Level Of Thermic Fluid
The Visual Level Indicator & Float Actuated Level Switch Fitted In Expansion Tank Signals Alarm In Case Of Low Level Thrermic Fluid In The System.

5. Thermal Fluid Pump Moter Trip
In Case Of Thermic Fluid Pump Motor Trip, Electrical Interlocks Cut-Off ID/FD Fan.

6. Power Failure.
Diesel Engine Drive Keeps Thermic Fluid Moving In The System To Prevent Its Degradation & Overflow.

7. Excess Furnace Bed Temperature
Digital temperature indicator cum controller senses furnace bed temperature & cut off ID/FD fan above set value (for FBC unit).

 

Thermic Fluid Heater-Vertical
The Vertical Four Pass Thermic Fuild Heater Is Situated For Various Industries Across India & Abroad In This Rapidly Changing & Undependable Energy Situations. Shivotherm Generous Design Of Vertical Heaters Coupled With Integra Furnace Gives You An Assurance Of The Rated Output On Any Solid Fuels Like Coal, Wood, Lignite, Husk, Bagasse, Pet Cake, Saw Dust, Etc. Without Compromising On Performance.

Shivotherm Can Deliver Sustainable Solution To Meet Your Process Requirement & Thus Improves Process Consistency & Reduce Downtime Leading To Further Increase In Profitability.

 

Efficiency At Its Peak

Fluidised Bed Combustion.
Fbc Technology Ensure Complete , Combustion, Help Homogenous Mixing Of Fuel, Maintain Uniform Bed Temperature & Leave Low Un-Burnt Fuel, Guaranteeing 5 To 7% Higher Efficiency Than Any Other Combustion System.

Air Pre Heater (Aph)
A Uniquely Designed Aph Recover Waste Heat From Flue Gases And Passes It To Combustion Chamber. This Increase Efficiency By 3 To 4% Also Reduce Flue Gas Temperature At Id Fan Which In Turn Reduce Volume Of Air Handled Resulting In Lower Power Consumption And Ensure Higher Life Of Id Fan.

Blance Draft
System Ensure Minimum Infiltration Of Unwanted Air Through Doors And Fresh Air Passes Through Aph Ensure Maximum Fuel To Heat Operating Efficiency For Any Commercial Grade Of Different Fuels.